混凝土墻內管路敷設工程技術交底-建筑安裝.doc
進入下載頁
一、 施工準備
(一) 混凝土墻內PVC管施工準備
1、 作業條件
在土建墻體、梁、柱鋼筋綁扎完成后,支立模板前進行。
2、 材料要求
(1) PVC管的材質必須合格,氧指數≥27%,設計有待殊要求時必須符合設計要求。進場材料必須有產品合格證,以及有效的氧指數檢測報告。
(2) 外觀檢查,管材內外壁光滑,無凸棱凹陷、氣泡等缺陷。
(3) 用卡尺測量內外徑必須符合國家標準,管壁厚度均勻一致。
各種附件如燈頭盒、開關插座盒、管接頭、盒接頭、粘合劑等必須使用配套的阻燃制品,同時應有出廠合格證、“CCC”認證
First, construction preparation
(A) concrete wall PVC pipe construction preparation
1, operating conditions
In the civil walls, beams and columns of reinforced banding is completed, the template before the Legislative branch.
2, material requirements
(1) PVC pipe material must be qualified, the oxygen index of ≥ 27%, designed to be special requirements must meet the design requirements. Admission materials must have a product certificate, and an effective oxygen index test report.
(2) inspection of the exterior wall of tubes inside and outside the smooth, non-convex edge dents, bubbles and other defects.
(3) in diameter with a caliper must meet national standards, uniform wall thickness.
Accessories such as lamp boxes, switch socket boxes, fittings, box joints, adhesives, etc. must use flame-retardant products supporting the same time, the factory proper certificate, "CCC" certification